  • Seismic zones map – France

    What are the French seismic zones according to Eurocode 8 ?

    In France, the division is specified in the law (not in the national annex). The French metropolitan area is divided into four seismic zones identified from 1 to 4 (The map below was created from this data).

    Zone1234
    SeismicityVery lowLowModerateMedium
    Seismicityagr0.4 m/s20.7 m/s21.1 m/s21.6 m/s2
    Seismic zoning of France (2015-2024)

    The French overseas departments, overseas territories and overseas collectivities each have a specific seismicity.

    ZoneFrench GuianaReunion IslandMayotte IslandMartinique IslandGuadeloupe Island
    SeismicityVery lowLowModerateStrongStrong
    Reference peak ground acceleration on rock >agr0.4 m/s20.7 m/s21.1 m/s23.0 m/s23.0 m/s2
    Seismicity of overseas departments
    ZoneSaint Pierre and MiquelonNew CaledoniaWallis and FutunaSaint MartinSaint Barths
    SeismicityVery lowModerateStrongStrongStrong
    Reference peak ground acceleration on rock >agr0.4m/s21.1m/s23.0m/s23.0m/s23.0m/s2
    Seismicity of overseas territories and overseas collectivities

    Is my new building concerned ?

    You can check if your building is concerned on the french regulations on LEGIFRANCE.
    Here is the summary:

    Zone/Importance classNormal riskSpecial risk
    IIIIIIIV
    Zone 1NoYes
    Zone 2NoYes
    Zone 3NoYes
    Zone 4NoYes
    Zone 5NoYes

    Example of results given by the software Eurocodes Zoning

    B1 – Localization

    • Coordinates in World Geodetic System 1984 (WGS84) 3.5332°, 45.7153°
    • Coordinates in French Geodetic System 1993 (Lambert 93) 741482m, 6512993m

    Address D 304A, 63120 Sauviat, Auvergne-Rhône-Alpes


    B2 – Altitudes

    Distances / DirectionAt the place of construction500m1000m
    North436 m 360m407m
    Northeast 405m465m
    East456m473m
    Southeast 419m446m
    South449m476m
    Southwest 432m411m
    West360m468m
    Northwest 403m452m

    B3 – Building

    • Type of building: monumental building
    • Design working life category: 100 years
    • Max height: 15.0 m
    • Orientation from North: 80°

    B4 – Terrain categories

    Sectors1234
    CategoriesIIIaIVIVIV
    Radius R of the angular sector 593m

    C1 – Snow

    NF EN 1991-1-3/NA (may 2007) + A1 (july 2011)

    • Zone : A2(sk,0 = 0.45 kN/m²)
    • Criteria for zoning : PUY-DE-DOME (63)
    • Characteristic value of snow on the ground at the relevant site : sk,436 = 0.686 kN/m²
    • Ground snow load with a return period of 100 years : s100 ans = 0.774 kN/m²
    • Design value of exceptional snow load on the ground : sad = 1.0 kN/m²

    C2 – Vent

    NF EN 1991-1-4/NA (march 2008) + A1 (july 2011) + A2 (september 2012) + A3 (april 2019)

    • Zone : 2(vb,0 = 24.0 m/s)
    • Criteria for zoning : PUY-DE-DOME (63)
    • Zone cdir : 1
    Sectors1234
    Sector definition from  35 °  to  125 ° from  125 °  to  215 ° from  215 °  to  305 ° from  305 °  to  35 °
    Fundamental value of the basic wind velocity  vb,0 24.0m/s
    Shape parameter  K 0.2
    Exponent n0.5
    Annual probability of exceedence p0.01
    Probability factor  cprob 1.038
    Directional factor  cdir 0.71.01.01.0
    Basic wind velocity  vb 17.4m/s24.9m/s24.9m/s24.9m/s
    Reference roughness length  z0,II 0.05m
    Roughness length  z0 0.2m1.0m1.0m1.0m
    Terrain factor  kr 0.2090.2340.2340.234
    Height above ground z15.0m
    Minimum height  zmin 5.0m15.0m15.0m15.0m
    Roughness factor  cr(z) 0.9040.6350.6350.635
    Orography factor  * co(z) 1.01.01.01.0
    Mean wind velocity  vm(z) 15.8m/s15.8m/s15.8m/s15.8m/s
    Turbulence factor  kl 0.970.8540.8540.854
    Standard deviation of the turbulence  σv 3.544m/s4.989m/s4.989m/s4.989m/s
    Turbulence intensity  Iv(z) 0.2250.3150.3150.315
    Air density  ρ 1.225kg/m3
    Exposure factor  ce(z) 2.1021.2921.2921.292
    Peak velocity pressure qp(z) 392.0N/m2491.5N/m2491.5N/m2491.5N/m2
    Peak wind velocity for Serviceability Limit States  vp(z),SLS 91.1km/h102.0km/h102.0km/h102.0km/h
    Peak wind velocity for Ultimate Limit States  vp(z),ULS 111.5km/h124.9km/h124.9km/h124.9km/h

    Here, the orography factor is calculated according to Procedure 1, for an orography consisting of obstacles of various heights and shapes. This type of orography is the most frequently encountered.However, if the building is in a case of orography consisting of well individualized obstacle (isolated hills and ridges or cliffs and escarpments) the orography factor must be calculated according to the procedure 2. According to EN 1991-1-4 §4.3.3(1), the calculated orography factor (1.018) is not taken into account because it does not increase wind velocities by more than 5%%.


    C3 – Seism

    Code of the Environment – Article D563-8-1 (09/01/2015)

    JORF n°0248 du 24/10/2010 texte N°5

    • Zone : 3(1.1 m/s²)
    • Criteria for zoning : Sauviat, Puy-de-Dome (63)
    • A seismic analysis may be required for this building.